SOLAR H1Z2Z2-F (PV1-F)

H1: Harmonized standards

Z2: Insulation low-smoke, zero-halogen compound, LSHF

Z2: Оuter sheath low-smoke, zero-halogen compound, LSHF

F: Thin copper conductor coated with a thin layer of tin 

 

CONSTRUCTION

  1. Thin copper conductor coated with a thin layer of tin
  2. Insulation low-smoke, zero-halogen compound, LSHF
  3. Оuter sheath low-smoke, zero-halogen compound, LSHF 

 

APPLICATION

SOLAR is intended for external and internal electrical connections in network photovoltaic systems of solar power plants in the absence of danger of mechanical damage, at a core heating temperature of up to 90 °C load.

 

TECHNICAL DATE

 

Standard cable:

  • ЕАEU
  • АМ-016/S.A.-0085-2023,
  • ТР-ТС-004/2011,
  • ГОСТ 31996-2012, ГОСТ 24888-81

Standard of Conductors for cables:

  • ЕАЭС / ЕАEU
  • АМ-016/S.A.-0085-2023
  • ТР-ТС-004/2011,
  • ГОСТ 22483-2012 (IEC 60228:2004 )

Standards for insulation thicknesses, shells and voltage tests:

  • ЕАEU
  • АМ-016/S.A.-0085-2023
  • ТР-ТС-004/2011,
  • ГОСТ 23286-78 (VDE 0100-430)

Standard Fire Safety Requirements:

  • ЕАEU
  • АМ-016/S.A.-0085-2023
  • ТР-ТС-004/2011,
  • ГОСТ 31565-2012 (IEC 60332-1-2)

Insulation material: Insulation low-smoke, zero-halogen compound, LSHF

Insulator Colour: DIN 47100

Working Temperature: -30C0/+90 C0

Max. Working Temperature: +120 C0

 

Working Voltage: Nominal variable voltage 0,66/1 max 1,2kV

Test Voltage: 6.5kV

 

Working Voltage: 1,5Kv max 1.8kV

Test Voltage: 15kV

 

Warranty life of the cable: 5 years after entering into exploitation, In the proper installation and working conditions

Design life: Not less than 30 years

Bending min. diameter: 5xD