NAYY, YAVV PVC FILLER (АВВГ-ПВX Наполнитель)

N: Harmonized standards

A: Aluminium conductor

Y: PVC insulation

Y: PVC outer sheat 

 

CONSTRUCTION

  1. Solid or Stranded aluminium conducto
  2. PVC insulation
  3. PVC filler
  4. PVC outer sheat

APPLICATION

Power centers, switch and industrial facilities, as power cable on local energy distribution; and also place which have no mechanic damage risk, in outside and inside, underground or cable channels․

 

TECHNICAL DATE

Standard cable:

  • ЕАEU
  • АМ-016/S.A.-0085-2023,
  • ТР-ТС-004/2011,
  • ГОСТ 16442-80

Standard of Conductors for cables:

  • ЕАEU
  • АМ-016/S.A.-0085-2023,
  • ТР-ТС-004/2011,
  • ГОСТ 22483-2012 (IEC 60228:2004)

Standards for insulation thicknesses, shells and voltage tests:

  • ЕАEU
  • АМ-016/S.A.-0085-2023,
  • ТР-ТС-004/2011,
  • ГОСТ 23286-78 (VDE 0100-430)

Standard Fire Safety Requirements:

  • ЕАEU
  • АМ-016/S.A.-0085-2023,
  • ТР-ТС-004/2011,
  • ГОСТ 31565-2012 (IEC 60332-1-2)

Insulation material: PVC

Insulator Colour: DIN 47100

Working Temperature: -30C0/+70 C0

Max. Working Temperature: +70 C0

Working Voltage: 0,6/1kV

Test Voltage: 4.0kV

Warranty life of the cable: 5 years after entering into exploitation, In the proper installation and working conditions

Design life: Not less than 30 years

Bending min. diameter: 12xD